48
Acc time refers to the time for inverter to reach the max. frequency from 0.00Hz.
Dec time refers to the time for inverter to lower to 0.00Hz from max. frequency.
P107 ACC time Factory Setting: change
SettingRange:0.1s~999.9s
P108 DEC time Factory Setting: change
F
The Default Acc/Dec time is the primary Acc time/ Dec. time. Other Acc time or
Dec time can be selected via external terminal.
P109 V/F maximum voltage Factory Setting: 380
SettingRange:V/F intermediate voltage-500.00Unit:0.1
P110 V/F fundamental frequency Factory Setting: 50
SettingRange:V/F intermediate frequency ~ max. frequencyUnit:0.1
P111 V/F intermediate voltage Factory Setting: change
SettingRange:V/F minimum voltage ~ V/F maximum Unit:0.1
P112
V/F intermediate frequency Factory Setting: 2.5
SettingRange:V/F minimum frequency ~ V/F fundamental Unit:0.1
P113
V/F minimum voltage Factory Setting: 15
SettingRange:0.0 ~ V/F intermediate voltage Unit:0.1
P114
V/F minimum frequency Factory Setting: 1.25
SettingRange:0.0 ~ V/F intermediate frequencyUnit:0.1
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul