EasyManua.ls Logo

Janson Controls FC100-2S-1.5G - Group P6: PID Control

Default Icon
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84
Action instruction:
1, Press K1 to startup the inverter and the potentiometer will set output
frequency.
2Press K3, PLC to startup, and from the segment 1 PLC program running
one circle and then ceasing
3If the program is runningpress K3, or if there is a fault, and the inverter
is ceasing, when the fault is solved, press K1 and the inverter will running
forward as the program.
4,If P500 is 1 and the program is not memory, so the running will start from
the very beginning.
Group P6: PLC Control(Special Operation)
Default value 0
PID starting mode
P600
Setting Range:0~1 Unit:1
The inverter can be used to exercise process control, e.g. flow rate, air volume
or pressue.
The terminal AV/AI input signal or parameter setting is used as a
set point and the terminal AV/AI input signal also can used as a feedback value
to constitute a feedback system for PID control.
Explanation:0: PID disable PID can not use.
1: PID start(PID is working despite the external signal input, and
keeps being valid without external input.)
2: PID starts up on condition; (PID will start when certain external
input is ON.)
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul

Table of Contents

Related product manuals