78
Default value 0.5
Constant-speed torque limiting time
P429
Setting Range:0~999.9S Unit:0.1
Default value 0
P430
Setting Range:0~2.00S Unit:0.1
This parameter sets frequency reached width, for details, refer to P425-F426
introductions
Width of arrive of frequency in hqsteretic loop
.5
Default value 0
Default value 0
Jump Frequency 1
Jump Frequency 2
P431
Setting Range:0~frequency upper limit Unit:0.1
Setting Range:0~frequency upper limit Unit:0.1
P432
Default value 0.5
Jump frequency hysteresis loop width
Setting Range:0~2.0 Unit:0.1
If machine resonance occurred at a certain frequency, we can use the
frequency jump function to skip the resonance point. t!20OtJ support 2 jump
frequencies by parameter P431 and P432.
Frequency jump hysteresis loop width can be set through P433 as below:
P433
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul