RTU mode:
Format of enquiry message:
Address
01H
Function
06H
Data Address
01H
00H
Data Content
17H
70H
CRC CHK Low
86H
CRC CHK High
22H
Format of response message:
SIX
.
Address
0
1
Function
0
6
Data address
0
1
0
Data Content
LRC Check
7
END
CR
LF
For example: Driver address 01H, writes 6000 (1770H) into the internal setting
parameter 0100H of driver.
Format of response message
Character string
LRCCheckofASCIImode
Format of enquiry message
Character string
0
1
7
7
0
1
SIX
.
Address
0
1
Function
0
6
Data address
0
1
0
Data Content
LRC Check
7
END
CR
LF
0
1
7
7
0
1
Address
01H
Function
06H
Data Address
01H
00H
Data Content
17H
70H
CRC CHK Low
86H
CRC CHK High
22H
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul