57
=3 VF control model;
=5 Step by step motor parameter detection model;
=6 Continuous motor parameter detection model;
=8 Theoretical calculation PI parameter model.
VC-Sel
=0 full-order mathematic model;
=1 voltage model;
=2 improved voltage model;
=3 improved full-order mathematic model.
FL-Limit
Flux linkage limit of motor.
WC-Set
Voltage WC.
Run-Mode
Run mode. Default is CVT.
UINST
Command voltage, you need to reduce this value to 0.85 times of
Vin when inverter is stop.
F-Limit
To set the stopping frequency according to user requirement,
inverter will stop running automatically as setting. Default is
50Hz.
D-Mode
For choose the dry out protection mode. When water sensor is
applied, dry protection mode should be set to detect dry
protection. Default is DETECT.
D-Power
Dry protection power, which shall be reset when the load power
rating is lower than Solar pumping inverter. Recommended value
is 40% of the rated output power of Inverter. For example, the
D-Power of 55kW pump is 22000.
D-Time
Dry out recovery time, under auto dry out mode, after the warning
of dry out and inverter shut down, the duration from shut down to
restart. Default value is 30. Default duration is 30 minutes.
T-DJ
Dry checking time (Unit is S).