LX Series Unit Ventilator Controller User's Guide 39
Selecting Fresh Air Damper Control for Ventilation Only
(without Free Cooling)
The Fresh Air Damper is closed during unoccupied periods. This diagram shows
damper control during:
Standby, Occupied and Bypass Modes; or,
Occupied Mode when free cooling is not in use or is disabled. Free cooling is not
in use whenever the free cooling output is less than minimum fresh air output.
Fresh_Air_Damper_Mod
Proportional Control
Min_Fresh_Air_Enable
Fresh air minimum
input
CO2 PID
Control
SCPTlimitCO2
Select the
Greatest
MAT Low Limit or SAT
Min Supply Temp.
CO2 Sensor Value
or
nviCO2
Select how the
Damper is controlled.
Can use either
of these two
outputs.
Ye
s
Fresh Air Damper
Is CO2 sensor
present?
Is damper position set
as the Fresh Air
Minimum Input?
No
Ye
s
No
Percentage of
fresh air intake
MA
T
OAT RAT
Fresh air minimum
input
MAT Mixed Air Temperature
SAT Supply Air Temperature
OAT Outside Air Temperature
RAT Return Air Temperature
Inputs to PID Control
Inputs to Proportional Control
UCPTminOutdoorAir
Is no limitation on
fresh air intake is
checked?
Ye
s
SAT Min Supply Temp.
No
vent
Figure 15: Ventilation Process

Table of Contents

Other manuals for Johnson Controls LX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls LX Series and is the answer not in the manual?

Johnson Controls LX Series Specifications

General IconGeneral
BrandJohnson Controls
ModelLX Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals