LX Series Unit Ventilator Controller User's Guide 93
nvoFanSpeed
This network variable output sends the fan speed.
Type: SNVT_switch (95)
nvoHwInputx
Numbered following the input number. For example, nviHwInput1, nvoHwInput2.
The network variable output sends the input value over the network with their own
changeable SNVT type.
Type: Changeable
nvoOccState
This network variable output sends the occupancy state used by the unit ventilator
object.
Type: SNVT_occupancy (109)
nvoUValarm
Table 31 describes the nvoUValarm parameters.
Type: SNVT_state_64 (165)
Format: UNVT_uv_alarms
Table 31: nvoUValarm (Part 1 of 3)
Programmatic Name Bit
Number
Meaning When Bit Is Set
nviSpaceTempHeartBeat 0 Heartbeat failure reported from nviSpaceTemp.
nviApplicModeHeartBeat 1 Heartbeat failure has occurred in nviApplicMode.
nviSetPtOffsetHeartBeat 2 Heartbeat failure has occurred in nviSetPtOffset.
nviOccCmdHeartBeat 3 Heartbeat failure has occurred in nviOccCmd.
nviWaterTempHeartBeat 4 Heartbeat failure has occurred in nviWaterTemp.
nviHotWaterHeartBeat 5 Heartbeat failure has occurred in nviHotWater.
This network variable input transmits the water
state: hot or cold.
nviSupplyTempHeartBeat 6 Heartbeat failure has occurred in nviSupplyTemp.
nviFanStateHeartBeat 7 Heartbeat failure has occurred in
nviFanSpeedCmdState.
nviEconEnableHeartBeat 8 Heartbeat failure has occured in nviEconEnable.
nviSheddingHeartBeat 9 Heartbeat failure has occurred in nviShedding.
nviSlaveHeartBeat 10 Heartbeat failure has occurred in nviSlave.
nviOutdoorTempHeartBeat 11 Heartbeat failure has occurred in nviOutdoorTemp.
nviSpaceRHHeartBeat 12 Heartbeat failure has occurred in nviSpaceRH.
nviOutdoorRHHeartBeat 13 Heartbeat failure has occurred in nviOutdoorRH.
nviCO2HeartBeat 14 Heartbeat failure has occurred in nviCO2.
nviReturnTempHeartBeat 15 Heartbeat failure has occurred in nviReturnTemp.
nviMixAirTempHeartBeat 16 Heartbeat failure has occurred in nviMixAirTemp.
nviSpaceEnthHeartBeat 17 Heartbeat failure has occurred in nviSpaceEnth.