LX Series Unit Ventilator Controller User's Guide 97
nvoTerminalLoad
This network variable output sends the energy demand of the fan coil in
percentage. Positive values are cooling demand and negative values are heating
demand.
Type: SNVT_lev_percent (81)
nvoUnitStatus
This network variable output sends the following simultaneously:
• operating mode
• primary heating state as a percentage
• secondary heating state (if relevant) as a percentage
• cooling state as a percentage
• fan state as a percentage
• unit ventilator alarm state
Type: SNVT_hvac_status (112)