LX Series Unit Ventilator Controller User's Guide 97
nvoTerminalLoad
This network variable output sends the energy demand of the fan coil in
percentage. Positive values are cooling demand and negative values are heating
demand.
Type: SNVT_lev_percent (81)
nvoUnitStatus
This network variable output sends the following simultaneously:
operating mode
primary heating state as a percentage
secondary heating state (if relevant) as a percentage
cooling state as a percentage
fan state as a percentage
unit ventilator alarm state
Type: SNVT_hvac_status (112)