Hardware Installation—IFC-200 Hardware Installation Procedures 41
IMPORTANT: Do not apply AC power or batteries until the system
is completely wired and ready for testing.
FIG2-25
1
2
3
654
789
*
0#
ABC DEF
GH I J KL M NO
PRS TUV WXY
Q Z
.
ENTER
DET MOD
1 2 3 4
NR45-24
GC12550
12 VDC
55-AH
Battery
GC12550
12 VDC
55-AH
Battery
120 VAC, 50/60 Hz
Primary Power Source
Hot Neutral
Cut terminals from IFC-200
battery cable connected to J3.
Use wire nuts.
J3
-
+
Cut JP2
to disable
internal
charger.
JP2
Figure 34: Remote Battery Charger Connection