5.2.7 Other Indications
In Normal Condition
Defrost
(for
&RROLQJ+HDWLQJ
Unit Only)
Defrost Operation
7KH³),/7(5'()´LQGLFDWRU\HOORZLV
turned ON during the defrosting. The louver
is stationary.
The louver indication of LCD continues to
be activated.
FILTER/DEF
(TIWM006B21S
to TIWM012B21S)
(TIWM015B21S
to TIWM030B21S)
The figure shows for TIWM015B21S to TIWM030B21S.
FILTER/DEF
Operation Stoppage during
Defrosting Operation
7KH581LQGLFDWRURUDQJHLVWXUQHG2))
when pressing “Off
” switch during the
defrosting.
7KHRSHUDWLRQFRQWLQXHVZLWKWKH³),/7(5
'()´LQGLFDWRU\HOORZWXUQHG21DQGWKH
XQLWZLOOEHVWRSSHGDIWHU¿QLVKLQJGHIURVW
operation.
Filter
Filter Sign
7KHDLU¿OWHUZLOOQHHGWREHFOHDQHGZKHQ
WKH³),/7(5'()´OLJKWWXUQV\HOORZ
This occurs when the operation time has
accumulated 200 hours.
After cleaning, point the transmitter towards
the receiver and press “Reset
” button to
WXUQ2))WKH³),/7(5'()´LQGLFDWRU
FILTER/DEF
(TIWM006B21S
to TIWM012B21S)
(TIWM015B21S
to TIWM030B21S)
The figure shows for TIWM015B21S to TIWM030B21S.
FILTER/DEF
In Abnormal Condition
Abnormal
 7KH581LQGLFDWRURUDQJHZLOOÀDVK
VHFRQG21VHFRQG2))ZKHQ
a fault is generated or a safety device
activates during TEST RUN or normal
operation.
The type of an alarm code is determined
E\KRZPDQ\WLPHVLQVHTXHQFHLWÀDVKHV
Example
"FILTER/DEF" (yellow lamp)
Alarm
3 5
"TIMER" (green lamp)
"TIMER" flashes 3 times
(0.5 second ON / 0.5 second OFF)
“FILTER/DEF" flashes 5 times
(0.5 second ON / 0.5 second OFF)
These indications are repeated until
the alarm is reset.
Power
Failure
 $OOWKHLQGLFDWLRQVDUH2))
Once a power failure has occurred, the unit will not restart even though power is
restored. Repeat the starting procedure.
In the case of instantaneous power failure within 2 seconds, the unit will be started
again automatically.
Electric
Interference
$XQLWVKXWGRZQZLWKDOOLQGLFDWRUV2))LVFDXVHGE\HOHFWURQLFLQWHUIHUHQFHQRLVH7KH
micro-computer was activated, thus setting the process in motion. Repeat the starting
procedure.
NOTE:
During heating operation, the fan speed may be changed to low due to air inlet thermistor control. However,
the indication is not changed.
Item Indicator
Indication
Color
)ODVKLQJ7LPHV
Tens Digit TIMER Green 7HQVGLJLWLVLQGLFDWHGE\QXPEHURIÀDVKLQJWLPHV
Unit Digit
),/7(5
'()
Yellow
8QLWGLJLWLVLQGLFDWHGE\QXPEHURIÀDVKLQJWLPHV
Alphabet
$OSKDEHWLVLQGLFDWHGE\QXPEHURIÀDVKLQJWLPHVDVIROORZV
A
...
WLPHV%
...
WLPHV&
...
12 times