Condenser screen
Figure 19: Condenser screen
The condenser screen displays the air-cooled condenser with an animation of heat ejection out of
the fan deck.
Table 28: Display only fields
Field name Description
Condenser saturation
temperature
The saturation temperature in the condenser, determined from the condenser pressure
Condenser small temperature
difference
The difference between the discharge saturation temperature and the outside ambient air
temperature. Discharge saturation temperature is determined from the discharge pressure.
Condenser pressure The refrigerant pressure in the condenser
Condenser liquid temperature The temperature of the refrigerant in the condenser
Subcooling temperature The difference between the condenser saturation temperature and the condenser liquid
temperature
Active subcooling setpoint The active subcooling setpoint
Condenser drain valve
command
The position command to the condenser drain control valve in percent of travel with 0% full
closed to 100% full open
High pressure switch (open/
closed)
The present position of the high-pressure switch. This indicates open when a high-pressure
fault is present.
Condenser fan speed
Command 1
Command signal to condenser fan speed for group 1A*
51YVAM with OptiView Control Center