Table 50: Display only fields
Field name Description
Voltage Total Harmonic
Distortion L1, L2, L3
The total harmonic distortion (THD) for each of the voltage lines as calculated by the VSD
Input Current Total Demand
Distortion L1, L2, L3
The total dynamic distortion (TDD) for each of the supply current lines as calculated by the
VSD.
Input Job Full Load Amps The job input FLA limit within a range limited from 10% to 100% of the drive nominal input
current at nominal line voltage
Table 51: Display only fields: LED
LED name Description
Motor Run If the digital output from the controls is commanding the motor to run
VSD Fault The VSD is reporting a fault over the communications link or by logic low at the hardwired
digital input
Table 52: Active input current limit details
Current limit control
source
Active input displayed
Local
Lowest of:
• Local input current limit
• Pulldown demand limit, when is runtime < pulldown demand time
BAS BAS input current limit setpoint, raw unlimited value from GPIC
0 V to 10 V
Lowest of:
• Local input current limit remote analog current limit
• Pulldown demand limit, when run time is < pulldown demand time
4 mA to 20 mA
Lowest of:
• Local input current remote analog current limit
• Pulldown demand limit, when runtime < pulldown demand time
PWM
Lowest of:
• Local input current limit remote PWM current limit
• Pulldown demand limit, when runtime < pulldown demand time
Table 53: Programmable fields
Name Access Description
Local Input Current Limit Operator
Specifies the maximum allowed input current as a percentage of job FLA.
When the input current reaches this value, the input current override takes
effect.
Pulldown Demand Limit Operator
Specifies the current limit value as a percentage of FLA to which the chiller
is limited during the specified pulldown limit time. This value overrides the
input current limit value during this time period. Provides energy savings
following chiller start-up. Pulldown demand limit is ignored in BAS (ISN)
control source because the BAS system algorithmically resets current limit as
required in that operating mode.
Pulldown Demand Time Operator
Set a period of time for which the pulldown demand limit to be in effect after
the chiller starts.
YVAM with OptiView Control Center68