Table 66: Display only fields
Control Field and LED name Description
Active current limit
Displays the present active current limit setpoints used for input
current limit control
Local current limit Displays the present local current limit setpoint
Pulldown demand limit
active (LED)
Indicates the pulldown demand limit is active
Pulldown demand limit Displays the pulldown demand input current limit setpoint
BAS current limit Displays the BAS input current limit setpoint
Remote analog current
limit
Displays the analog input current limit setpoint
Input current limit
Remote PWM current limit Displays the digital PWM input current limit setpoint
Active cooling setpoint
Displays the calculated active cooling setpoint that is to be
maintained by the capacity control
Selected cooling setpoint
Displays the present cooling setpoint.
When variable water outlet control is disabled, the selected cooling
setpoint is set based on the cooling setpoint control source.
When variable water outlet control is enabled, the local and
remote cooling setpoints is ignored and the selected cooling
setpoint is set based on the outside ambient air temperature.
Local cooling setpoint Displays the present local cooling setpoint
BAS cooling setpoint Displays the BAS cooling setpoint
Remote analog cooling
setpoint
Displays the analog cooling setpoint
Cooling setpoint control
Remote PWM cooling
setpoint
Displays the digital PWM cooling setpoint
Table 67: Programmable fields
Button Access Description
Select run/stop Operator
The run/stop control source from:
Local
BAS
Hardwire
Select cooling Operator
The cooling control source from:
Local
BAS
0 V to 10 V
4 mA to 20 mA
PWM
[Cooling setpoint
control] Remote
setpoint minimum
Operator
The minimum remote cooling setpoint.
Range: 0°F (-17.8°C) to 200°F (93.3°C)
Default: 100°F (37.7°C)
79YVAM with OptiView Control Center