JVL Industri Elektronik A/S - User Manual - Ethernet for MAC and MIS motors 143
6.2 Commissioning
6.2.7 Quick start guide
This section describes the steps to configure the Siemens ET200S PLC and TIA Portal
v11 software, so it can be used to control the drive.
Set IP address
1. If having a MAC motor then Connect the RS232 communication cable, and if having
a MIS/MIL motor then connect the RS485 communication cable.
2. Apply power to the motor, and make sure the PWR LED is lit.
3. Open MacTalk and select the "MAC00-EP (PROFINET)" tab.
4. Change the IP address, to one suitable for the network.
5. Press "Apply and save".
Installation
6. Connect an Ethernet RJ45-M12 cable to one of the interfaces on the ET200S and to
“L/A IN” and “L/A OUT” at the MAC module and “CN2” and “CN3” at the MIS/MIL
motors.
7. Connect power to the ET200S, and Ethernet patch cable from the PC with Siemens
TIA Portal v11 installed to the ET200S PLC.
8. Make sure power is applied to all devices.
Add the GSD file (contains info on the capabilities of the device)
9. In the Options menu of TIA Portal V11, select Install general station description file
(GSD).
10. In the "Install general station description file" window find and select the "GSDML-
V2.2-JVL-MAC00-EPX-yyyymmdd.xml" file, and click Install.
11. Follow the on screen instructions.
PLC configuration
12. Create a new project in TIA Portal v11 for your PLC, or open an existing project.
See Siemens documentation for more information.
13. In the Hardware catalog under Other field devices / PROFINET I/O / I/O / JVL
Industri Elektronik A/S / PNS should MAC00-EPx reside. See figure at next
page.