UL 1076 Compliance Notice
The KT-1 is UL 1076 Listed as a Commercial Proprietary Control Unit Accessory and Proprietary Burg-
lar Alarm Unit (Section 83.2), with EntraPass and Redundant Server, alarm system features, KT-300,
KT-400 Controllers, Kantech ioProx Proximity readers, and TRex request to exit devices other
sensor devices (temperature, water level, etc.) may be used as long as they are also UL 1076 Listed.
The EntraPass and Redundant Server shall be running at all time, and manned 24 hours a day, 365
days a year The EntraPass and Redundant Server will each have their own operator workstation.
Data processing equipment and office appliance and business equipment used as central supervisory
equipment station shall be listed to Information Technology Equipment - Safety-Part 1: General
Requirements - UL 60950-1.
Should the EntraPass and/or Redundant Server be replaced, a UL 60950-1 listed computer must be
used.
The following recommended system requirements apply to the EntraPass Server, Redundant Server,
Video Vault, Card Gateway, SmartLink, and Workstation:
Operating Systems: Window 2008/Windows 2012/Windows 7 Standard/Enterprise
Server Editions/Windows 8
Processor: Dual Core
4 GB RAM
Minimum free hard disk space: 20 GB
Color depth: 24-bit (16 million colors), required for Video Integration only
Screen resolution: 1024 x 768
AGP or PCI Express 8X graphics card with 64 MB memory and DirectX 9.0 support
Network Interface card: 10/100 Base-T network adaptor
Note: Actual requirements may vary based on your operating system and configuration.
The Central Supervisory Equipment shall employ supply line transient protection complying with the
Standard for Transient Voltage Surge Suppressors, UL 1449, with a maximum marked rating of 330 V.
The Central Supervisory Equipment shall employ signal line Transient protection complying with the
Standard for Protectors for Data Communications and Fire Alarm Circuits, UL 497B, with a max-
imum marked rating of 50 V.
The Central Supervisory Equipment shall employ that communication circuits and network com-
ponents connected to the telecommunications network shall be protected by secondary pro-
tectors for communication circuits. These protectors shall comply with the Standard for Secondary
Protectors for Communications Circuits, UL 497A. These protectors shall be used only in the pro-
tected site of the telecommunications network.
The Central Supervisory Equipment shall be installed in a temperature controlled environment. A
temperature controlled environment is defined as one that can be maintained between 14° - 10°C
(55° - 95°F) by HVAC system. Twenty-four hours on standby power shall be provided for the HVAC
system. The standby power system for the HVAC system may be supplied by an engine driven gen-
erator alone. A standby battery is not required to be used.
A marking to identify the application and signaling function of the product is located on the inside of
the unit (inner door sticker).
For certified commercial proprietary control unit accessory applications, the requirements of UL
1076, Commercial Proprietary Control Unit Accessory also apply.
The reader(s), that is(are) designated to arm or disarm the alarm system, must be within the secured
side of the customer premises.
©Copyright, 2016, all rights reserved
48

Table of Contents

Other manuals for Kantech KT-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kantech KT-1 and is the answer not in the manual?

Kantech KT-1 Specifications

General IconGeneral
CommunicationRS-485
Max. Number of Doors1
TypeDoor Controller
Power Supply12 VDC
Reader TechnologyWiegand
Operating Voltage12 VDC

Related product manuals