Installation, Connection & Power
Overview
Installation of the KT-1 varies with the type of unit: KT-1 or KT-1-PCB. Installation is
also dependent on the selection of the 12 V or PoE/PoE+ as the power source (see
Powering the KT-1 later in this section for more details).
Preparing to Install the KT-1
Locate an ideal indoor location for installation of the KT-1/KT-1-PCB while keeping
clear of electrical and communication devices. The KT-1 unit has been designed to
be mounted on a wall without any additional enclosures. The KT-1-PCB has been
designed to go into a cabinet.
The unit shall be mounted indoors in a secure location, providing normal tem-
perature and humidity. There should be 23 cm (8 in) clear space around all sides,
and a minimum of 33 cm (13 in) clear space in front of the unit. The location should
be easily accessible for servicing the equipment and it is recommended that con-
trollers be located close to the controlled doors.
Controllers must be located at a minimum distance of 2 m (6 ft) from any high
voltage equipment or wiring; electrical equipment susceptible of generating elec-
trical interference; at a minimum distance of 1 m (3 ft) from telephone equipment
or lines; and at a minimum of 8 m (25 ft) from any transmitting equipment. Physical
access, using keys on controlled doors, must be provided so that the KT-1 can easily
be accessed for servicing in case of malfunction.
Physical Installation:
Warning: It is the INSTALLER’S RESPONSIBILITY to route and secure the internal
wiring in such a manner (using tie wraps or equivalent means for fixing the cables)
that no cable may become in contact with the FRONT COVER of the METAL
ENCLOSURE.
© Copyright, 2016, all rights reserved
27