EasyManua.ls Logo

KB Electronics KBDA-24D - IODA Functions and Features

KB Electronics KBDA-24D
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
TABLE 12 IODA FUNCTIONS AND FEATURES
Multi-Function
Input Terminal Codes
Terminal Assignment
Multi-Function
Input
Terminals
1
(Digital Inputs)
Power
Supply
2
Multi-Function
Outputs
2
Analog
Outputs
2
Analog
Inputs
2
Relay
Outputs
3
0000: Preset Frequency
Operation
1
0001: Preset Frequency
Operation
1
0002: Preset Frequency
Operation
1
0003: Up Frequency
Command
(See Function
No. 7.14)
0004: Down Frequency
Command
(See Function
No. 7.14)
0005: Accel/Decel 2
(See Function
No. 7.16)
0006: Forward/Stop
Command
0007: Reverse/Stop
Command
0008: External Fault
0009: Reset
0010: N.O. Start
(2-Wire or
3-Wire Start/Stop)
0011: N.C. Stop
(3-Wire Start/Stop)
1 – 7 8: Common
9: +5 Volts
10: –5 Volts
11: Open
Collector 1
12: Common
13: Open
Collector 2
14: Common
15: Analog Out 1
16: Common
17: Analog Out 2
18: Common
19: Analog In 1
20: Common
21: Analog In 2
22: Common
23: RY1 N.O.
24: RY1 Common
25: RY1 N.C.
26: RY2 N.O.
27: RY2 Common
28: RY2 N.C.
Notes: 1. Multi-Function Input Terminals “1” – “7” can be programmed for: 7 Preset Frequencies*, Up or Down Frequency Command,
Accel/Decel 2, Forward/Stop, Reverse/Stop, External Fault, Reset, and 2-Wire/3-Wire Start/Stop. 2. Common Terminals 8, 12, 14, 16, 18, 20,
and 22 are all internally wired together and can be used with any of the Multi-Function Input Terminals “1” – “7”. 3. RY1 Common (Terminal
24) is the contact common only for Relay 1. RY2 Common (Terminal 27) is the contact common only for Relay 2.
*The 7 Preset Frequencies are obtained using a combination of Terminals 1, 2, 1+2, 3, 1+3, 2+3, 1+2+3.