Preparatory measures
© KEB, 2015-07 COMBIVERT R6-N Page4.1 - 7
4
10
Automatic
Restart
The COMBIVERT R6 can be adjusted by such way that the inverter restarts automatically
after an error case (e.g. broken phase line). System design must take this into account, if
appropriate, and additional monitoring or protective features added where necessary.
Not Short-Cir-
cuit Proof
(Supply)
The COMBIVERT R6 is not short-circuit proof at the power supply input ! If the I2t-protection
is adapted with a gR fuse, a conditional protection at supply input is possible. The short-cir-
cuit protection at DC output is if applicable ensured by internal or external aR respectively
gR fuses.
Conditionally
Short-Circuit
Proof
(Feedback)
The COMBIVERT R6 is conditionally short-circuit proof (EN 61800-5-1 / VDE 0160). After
resetting the internal protection devices, the function as directed is guaranteed.
Exception:
if an earth-leakage fault or short-circuit often occurs at the output, this can lead to a defect
in the unit.
Cyclic Acti-
vation And
Deactivation
With applications requiring the COMBIVERT R6 to be switched on and off cyclically, main-
tain an off-time of at least 5 min. Switching off during the initialization phase can cause
undenedconditions.IfyourequireshortercycletimespleasecontactKEB.
RCD (Resid-
ual Current
Operated Cir-
cuit-Breaker)
When using systems with RCD, the instructions or the requirements of VDE 0100 -T 530
(IEC 60364-5) must be observed. The recommended tripping current of the RCD type „B“
is 300 mA.