Protection functions
Unit of the pre-warning
Pre-warning period or level adjustable
Pre-warning possible via digital output
Function can be switched off
Automatic restart adjustable
Error without adjustable response
Message
Operator
values Message COMBIVIS
E.buS/ A.buS 18/93 Error!/warning! Watchdog - • • - • s
E.EEP 21 ERROR! EEPROM defective • - - - - -
E.EF/ A.EF 31/90 Error!/warning! ERROR external fault - • • - - -
Error ! 15 ERROR! Load shunt fault • - - - - -
E.nEt 3 ERROR! Mains • - - - - -
E. OC 4 ERROR! Overcurrent - • - - - -
E.OH/ A.OH 8/89 Error!/warning! Power module temperature - • - • • °C
E.OHI/ A.OHI 6/87 Error!/warning! Interior temperature - • • • • s
E.OL/ A.OL 16/99 Error!/warning! overload (Ixt) - • - • • %
E. OP 1 ERROR! Overvoltage - • - - - -
E. Pu 12 ERROR! defective in power unit • - - - - -
E.Puch 50 ERROR! Power unit code changed • - - - - -
E.Puci 49 ERROR! Power circuit unknown • - - - - -
Error: Power
circuit identi-
cation was
changed;
14 ERROR! power unit coding • - - - - -
E.SEt/ A.SEt 39/102 Error!/warning! Set - • • - - -
E.SYn 59 ERROR! Synchronization • - - - - -
E. UP 2 ERROR! Undervoltage - • - - - -
F.nEt 40 ERROR! mains frequency • - - - - -
3.6.1.1 Undervoltage
"Error ! Undervoltage "(E.UP) is triggered if the DC link voltage drop due to voltage dip or generally at low net-
work. The automatic restart can be activated for this error.
3.6.1.2 Overvoltage
"Error ! Overvoltage" is triggered if the DC link voltage increases beyond the overvoltage level.
3.6.1.3 Overcurrent
The "Error! Overcurrent“ (E.OC) is triggered, if the „OC tripping current“ (see technical data in the instruction
manual) is exceeded.
If this error occurs permanently, either the parameter setting is not correct or the COMBIVERT is defective.