Page 3.5 - 4 COMBIVERT R6-N © KEB, 2015-07
Regenerative adjustments
3.5.3 Deactivate regeneration
Ifthe active power exceedsthe level specied incS.06 the modulation is switched offafter puls off delay
(cS.05).
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.05 puls off delay 0F05h rw - - 0 32000 1 ms 200
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.06 puls off level 0F06h rw - - -10000 0 1 kW -0.8
3.5.4 Optimization for regeneration
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.04 switch off delay OSF rw np E -10 +10 1 – 0
Offsetofthemodulationwindowatthestartofthemodulationwithharmoniclter
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.07
mainssync.lterquality
0F07h rw np E 1 8 1 – 1
Thesmallerthevalue,thefastertheinternalmainssynchronisationfollowsthemainvoltagefrequencyuc-
tuations.
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.08 Kp - comm.choke 0F08h rw np E 7 13 1 – 10
Gain of the controlled variable at commutation choke.
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.09 Ki - comm.choke 0F09h rw np E 5 11 1 – 8
Controller speed at commutation choke.
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.11 Kp-harm.lter 0F0Bh rw np E 7 13 1 – 10
Gainofthecontrolledvariableatharmoniclter.
Parameter Addr. R PG E Min.
value
Max.
value
Res. [?] Default
cS.12 Ki-harm.lter 0F0Ch rw np E 5 11 1 – 8
Controllerspeedatharmoniclter.