Table 5 – Configuration codes
NOTE: Setting the options marked with asterisks does not comply with EN54-2
CODE FUNCTION COMMENTS
UXX CONFIGURATION UPDATE COUNT Number incremented each time access level 3 config
changed. Counter resets to 00 when 99 is reached.
C00 SOUNDER DELAY TIME = 30 SECONDS
Introduces a time delay before sounders operate.
Note: Only one delay period can be selected.
Delays will only be activated by selecting the "Ad" option
in the Access Level 2 (User) menu
C01 SOUNDER DELAY TIME = 1 MINUTE
C02 SOUNDER DELAY TIME = 2 MINUTES
C03 SOUNDER DELAY TIME = 3 MINUTES
C04 SOUNDER DELAY TIME = 4 MINUTES
C05 SOUNDER DELAY TIME = 5 MINUTES
C06 SOUNDER DELAY TIME = 6 MINUTES
C07 SOUNDER DELAY TIME = 7 MINUTES
C08 SOUNDER DELAY TIME = 8 MINUTES
C09 SOUNDER DELAY TIME = 9 MINUTES
C11 Z1 & Z2 DETECTORS TRIGGER AUTOMATIC RELEASE Coincidence detection selection options.
Only one option can be selected.
C12 Z2 & Z3 DETECTORS TRIGGER AUTOMATIC RELEASE
C13 Z1 &Z3 DETECTORS TRIGGER AUTOMATIC RELEASE
C14 Z1 & Z2 OR Z2 & Z3 OR Z1 & Z3 DETECTORS TRGGER
AUTOMATIC RELEASE
*C15 Z1 & Z2 & Z3 DETECTORS TRIGGER AUTOMATIC
RELEASE
C16 Z1 OR Z2 OR Z3 DETECTORS TRIGGER AUTOMATIC
RELEASE
C17 Z1 DETECTORS TRIGGER AUTOMATIC RELEASE
C18 Z2 DETECTORS TRIGGER AUTOMATIC RELEASE
C19 Z3 DETECTORS TRIGGER AUTOMATIC RELEASE
C21* DISABLE FIRE BUZZER
C22* DISABLE FIRE OUTPUT Fire relay.
C23 DISABLE FAULT OUTPUT Fault relay.
C24 DISABLE EARTH FAULT MONITORING
C25 PULSE R0V OUTPUT
C26 REMOVE AUX 24V ON SYSTEM RESET To enable resetting of systems using panels Aux supply.
C27 INDICATE EXTING RELEASED WHEN EXTING OUTPUT
IS ACTIVE
Rather than upon receipt of signal from flow switch.
C28 NO ACTIVATION DELAY UPON MANUAL RELEASE Delay remains active on automatic detection.
C29 EXTINGUISHANT OUTPUT CAN BE RESET DURING
IMMINENT PHASE
Allows extinguishant output to be reset before
countdown timer has expired for testing/commissioning
C2A LOCAL FIRE RELAY OPERATES UPON RELEASED
SIGNAL
Local fire relay operates only when extinguishant is
released rather than upon a fire condition
C2b* EXTINGUISHING OUPUT ON TILL RESET Extinguishant output remain on after release until panel
is reset. (from software version 1.2 onwards only)
C2C LOW PRESSURE SWITCH NORMALLY CLOSED Low Pressure switch input normally looks for open
contact closing on activation, enables normally closed
switch to be used. (from software version 1.2 onwards
only)
C2d
DELAY MAINS FALI INDICATION BY 30 MINUTES Cancelled if battery Low fault is indicated
C31 ZONE 1 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note: Any combination can be selected.
C32 ZONE 2 ALARM FROM DETECTOR DELAYED
C33 ZONE 3 ALARM FROM DETECTOR DELAYED
C41 ZONE 1 ALARM FROM CALL POINT DELAYED Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only.
Note: Any combination can be selected.
C42 ZONE 2 ALARM FROM CALL POINT DELAYED
C43 ZONE 3 ALARM FROM CALL POINT DELAYED
C61 ZONE 1 OPERATES THROUGH I.S. BARRIER Select only when detectors are connected via
compatible I.S. barriers.
Note: Any combination can be selected.
C62 ZONE 2 OPERATES THROUGH I.S. BARRIER
C63 ZONE 3 OPERATES THROUGH I.S. BARRIER
C71* ZONE 1 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the zone so that the
control panel can be used on older systems that had no
short circuit monitoring. Note: Any combination can be
selected.
C72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
C73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
C81* ZONE 1 NON-LATCHING Renders the zone self-resetting so that it can be used to
receive signals from other systems and will reset when
the input is removed. Note: Any combination can be
selected.
C82* ZONE 2 NON-LATCHING
C83* ZONE 3 NON-LATCHING
CA1 Z1 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
Input delay.
Note: Any combination can be selected.
CA2 Z2 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS