6-2 Generator/Controller Troubleshooting TP-5648 8/93
Rock and hold
Start/Stop
Switch to Start
Position. Does
Engine Crank?
Yes
No
Is LED2 lit
while Start/Stop
Switch is in
Start Position?
Yes
No
Check 10A fuse on
controller front panel.
Is fuse good?
Yes
No
Replace fuse. If
trouble persists,
check circuits
for shorts.
Is LED3 lit
while Start/Stop
Switch is in
Start Position?
Yes
No
Check/replace
Start/Stop Switch.
Check/service/re-
place battery and
battery connections.
Check/service/repair
battery charging
alternator.
Check/replace glow
plug solenoid.
Check/repair wiring
to P1-14, P1-9,
P2-4, and P2-6.
Go to A
(Sheet 2)
Is 12 VDC
present across
coil of relay K20
(wire 71 to GND)
while LED3 is lit?
Yes
Is 12 VDC
present across S
solenoid (wire
71A to GND) while
LED3 is lit?
Yes
Does starter
motor turn
while LED3 is lit?
Yes
Replace S
(starter)
solenoid.
Replace
circuit board.
No
No
Replace K20
relay.
Replace S
(starter) solenoid.
No
Replace
starter
motor.
Replace
circuit board.
Is 12 VDC
present across
starter motor
while LED3 is lit?
Start
(Engine
Stopped)
.
.
Rotate Emergency
Stop Switch Clock-
wise. Does LED2
light while Start/Stop
Switch is in Start
Position?
Yes
Someone
activated
Emergency
Stop
Switch.
Determine
why.
Is 12 VDC
present at P1-4
when LED3
is lit?
No
No
No
Check/repair
wiring between
P1-4 and K20.
Yes
Yes
Figure 6-2. Troubleshooting Flow Chart (Sheet 1 of 4)