13KR Electrical Defrost Unit Coolers (PN E108318_S)
TABLE 7B: RECOMMENDED EXPANSION VALVES FOR ELECTRIC DEFROST MODELS
MODELS
TXV
R404A R407A R448A
KR*14E-037[ ]{ }
SBFSE-AA-Z
EGSE-1/4-Z
SBFNE-AA-Z
EGNE-1/2-Z
SBFDE-AAA-Z
EGDE-1/4-Z
KR*24E-074[ ]{ }
SBFSE-A-Z
EGSE-1-Z
SBFNE-A-Z
EGNE-1-Z
SBFDE-AA-Z
EGDE-1/2-Z
KR*34E-111[ ]{ }
SBFSE-A-Z
EGSE-1-Z
SBFNE-A-Z
EGNE-1-1/2-Z
SBFDE-A-Z
EGDE-1-Z
KR*44E-148[ ]{ }
SBFSE-B-Z
EGSE-1-1/2-Z
SBFNE-B-Z
EGNE-2-Z
SBFDE-A-Z
EGDE-1-Z
KR*54E-185[ ]{ }
SBFSE-B-Z
EGSE-2-Z
SBFNE-B-Z
EGNE-2-Z
SBFDE-A-Z
EGDE-1-Z
KR*64E-220[ ]{ }
SBFSE-C-Z
EGSE-2-Z
SBFNE-B-Z
EGNE-3-Z
SBFDE-B-Z
EGDE-1 1/2-Z
KR*16E-035[ ]{ }
SBFSE-AA-Z
EGSE-1/4-Z
SBFNE-AA-Z
EGNE-1/2-Z
SBFDE-AAA-Z
EGDE-1/4-Z
KR*16E-045[ ]{ }
SBFSE-AA-Z
EGSE-1/2-Z
SBFNE-AA-Z
EGNE-3/4-Z
SBFDE-AA-Z
EGDE-1/3-Z
KR*26E-090[ ]{ }
SBFSE-A-Z
EGSE-1-Z
SBFNE-A-Z
EGNE-1-Z
SBFDE-A-Z
EGDE-1/2-Z
KR*36E-135[ ]{ }
SBFSE-B-Z
EGSE-1 -1/2-Z
SBFNE-B-Z
EGNE-2-Z
SBFDE-A-Z
EGDE-1-Z
KR*46E-180[ ]{ }
SBFSE-B-Z
EGSE-2-Z
SBFNE-B-Z
EGNE-2-Z
SBFDE-A-Z
EGDE-1-Z
KR*56E-192[ ]{ }
SBFSE-B-Z
EGSE-2-Z
SBFNE-B-Z
EGNE-2-Z
SBFDE-B-Z
EGDE-1 -1/2-Z
KR*66E-270[ ]{ }
SBFSE-C-Z
EGSE-2-Z
SBFNE-C-Z
EGNE-3-Z
SBFDE-B-Z
EGDE-2-1/2-Z
TXV selections are based on +25°F suction temperature, 10°F T.D., and 95°F liquid temperature,
105°F Condensing temperature and high side pressure drop of 10 PSIG.
NOTE 2: For R-507, replace the second ‘S’ with ‘P’ in R-404-A TXV. For example,
SBFSE-B-C (R- 404A)
becomes SBFPE-B-C and EGSE-1-1/2-C becomes EGPE-1-1/2-C (R-507)
For R-449A, use the same TXV as R-448A
For R-407F, use the same TXV as R-407A