12 Menu description
12.3 Menu 2 - RATE
12.3 Menu 2 - RATE
No. Submenu Page (Information) Values Preset
2.1 UNIT Measurement unit for the flow rate. Changing the
measurement unit affects the values in the oper-
ator and setup mode, the K-factor must be adjus-
ted accordingly.
mL: L; m
³
; g;
kg; ton; GAL;
bbl; lb; cf
L
2.2 TIME Time unit for calculating the flow rate (flow rate/
time unit):
/SEC = per second
/MIN = per minute
/HOUR = per hour
/DAY = per day
/SEC
/MIN
/HOUR
/DAY
/MIN
2.3 DECS Display format of the decimal values of the flow
rate
0
0.1
0.02
0,003
0.0004
0
2.4 K-F K-factor for flow rate 0.000010....
9999999
1
2.5 K-FD Display format of the decimal values of the K-
factor for flow rate
0
0.1
0.02
0,003
0.0004
0.00005
0.000006
0
2.6 MEAS Time in seconds to measure the pulses. The flow
rate is calculated from the number of measured
pulses during the selected time period.
1...10 1
Tab.8: Menu 2 - RATE
12.4 Menu 3 - METER
No. Submenu Page (Information) Values Preset
3.1 SIGN Output signal type PNP
NAMUR
PNP
Tab.9: Menu 3 - METER
12.5 Menu 4 - A-OUT
Note If the operating conditions require it, the minimum and maximum value of the output signal can be ad-
justed. However, an adjustment may only be made if the analogue output is deactivated.
Changing the values when the analogue output is activated can produce undesired measurement res-
ults and consequently damage to the unit.
No. Submenu Page (Information) Values Preset
4.1 MODE Activate or deactivate analogue output DISABLE
ENABLE
DISABLE
4.2 R.MIN Flow rate that generates the minimum output signal
(default = 4 mA)
0,000...
9999999
0
4.3 R.MAX Flow rate that generates the maximum output signal
(default = 20 mA)
0,000...
9999999.
Q
rated
*
4.4 T.MIN Minimum output signal
Note: The value can be adjusted if the analogue
output is deactivated.
0...9999 1365
18
OIE 24en-GB Edition 2022-01
Operating instructions