10 Related Documents
74 of 92
KSB Delta Macro
1983.843/04-EN
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-5-3-2-4 Response Message Message Everybody Service -
Flushing
2-5-3-3 Water stagnation monitoring - - - - -
2-5-3-3-1 Water stagnation monitoring Disabled Disabled Everybody Service -
Enabled
2-5-3-3-2 Source Flow sensor - Everybody Service -
Flow switch
Flow estimation (VFD)
2-5-3-3-3 Time of stagnation 0 … 7 d 24h Everybody Service -
2-5-3-3-4 Response Message Message Everybody Service -
Flushing with check run
2-5-3-4 Forced flushing - - - - -
2-5-3-4-1 Forced flushing Disabled Disabled Everybody Service -
Enabled
2-5-3-5 Flushing function - - Everybody Nobody -
2-5-3-5-2 Minimum flushing time 0 … maximum flushing time 10s Everybody Service -
2-5-3-5-3 Maximum flushing time Minimum flushing time … 999 s 60s Everybody Service -
2-5-3-5-4 Maximum flushing attempts in
24 hours
0 … 10 5 Everybody Service -
2-5-3-5-5 Stop temperature for flushing 0 … maximum temperature 20°C Everybody Service -
2-5-3-5-6 Flushing time for each pump 0 … 999s 10s Everybody Service -
2-5-4 Emergency power operation - - Everybody Nobody -
2-5-4-2 Maximum system load 1 … maximum number of pumps 1 Everybody Service -
2-5-4-3 Stop delay enabled/disabled Disabled Enabled Everybody Service -
Enabled
2-5-5 Discharge pressure monitoring - - Everybody Nobody -
2-5-5-1 High pressure alarm - - Everybody Nobody -
2-5-5-1-1 Maximum discharge pressure 0 … maximum pump head Maximum pump
discharge head
Everybody Service -
2-5-5-1-2 Delay time 0 … 60s 10s Everybody Service -
2-5-5-1-3 Selection of pump response Message Message Everybody Service -
Message and stop all pumps
2-5-5-2 Low pressure alarm - - Everybody Nobody -