Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-5-5-2-1 Minimum discharge pressure 0 … maximum pump head 0 Everybody Service -
2-5-5-2-2 Delay time 0 … 60s 10s Everybody Service -
2-5-5-2-3 Selection of pump response Message Message Everybody Service -
Message and stop all pumps
2-5-6 Pipe filling function - - - - -
2-5-6-1 Pipe filling function Disabled Disabled Everybody Service -
Enabled
2-5-6-2 Deviation from set-point 0 … set-point 10 Everybody Service -
2-5-6-3 Ramp-step for increasing set-
point
0 …10bar 0.1bar Everybody Service -
2-5-6-4 Maximum time on ramp-step 0 … 600s 60s Everybody Service -
2-5-6-5 Maximum number of attempts 1 … 10 3 Everybody Service -
2-5-7 Redundant system - - - - -
2-5-7-1 Redundant system role Master Master Everybody Service -
Slave
2-5-7-2 Redundant system scheduler Disabled Disabled Everybody Service -
Enabled
2-5-7-3 Redundant system scheduler -
start time hours
0…24h 0 Everybody Service -
2-5-7-4 Redundant system scheduler -
start time minutes
0 … 60min 0 Everybody Service -
2-5-7-5 Redundant system scheduler -
stop time hours
0…24h 0 Everybody Service -
2-5-7-6 Redundant system scheduler -
stop time minutes
0 … 60min 0 Everybody Service -
10.2.2.6 Accumulator
Table34: Accumulator parameters
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-6 Membrane-type accumulator - - - - -
2-6-1 Pressure-vessel accumulation Disabled Disabled Everybody Customer -
Enabled

Table of Contents

Related product manuals