10.2.2.7 Tank
Table35: Tank parameters
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-7 Tank - - Everybody Nobody -
2-7-1 Drinking water - - - - -
2-7-1-1 Drinking water filling - - - - -
2-7-1-1-1 Drinking water filling Disabled Disabled Everybody Service -
Enabled
2-7-1-2 Tank level - - - - -
2-7-1-2-4 Absolute height at 0 % 0 … absolute height at 100 % Position of sensor
above tank-bottom
Everybody Service -
2-7-1-2-5 Absolute height at 100 % Absolute height at 0 % … 2000cm 200cm Everybody Service -
2-7-1-2-6 Position of sensor above tank
bottom
0 … level at 20mA 20cm Everybody Service -
2-7-1-2-7 Low-water level 0 … low-water reset level 0,1 Everybody Service -
2-7-1-2-8 Low-water reset level Low-water level … critical water level 0,15 Everybody Service -
2-7-1-2-9 Critical water level Low-water level … high-water level 0,3 Everybody Service -
2-7-1-2-10 Level for reset critical water level Critical water level … high-water level 0,35 Everybody Service -
2-7-1-2-11 Start tank filling level Low level … stop tank filling level 0,5 Everybody Service -
2-7-1-2-12 Additional start tank filling level Low level … start tank filling level 0,4 Everybody Service -
2-7-1-2-13 Additional stop tank filling level Start tank filling level … stop tank
filling level
0,9 Everybody Service -
2-7-1-2-14 Stop tank filling level Start tank filling level … high-water
level
1 Everybody Service -
2-7-1-2-15 Level for reset high-water level Stop tank filling level … high-water
level
1,2 Everybody Service -
2-7-1-2-16 High-water level Stop tank filling level … according to
sensor type or level at 20mA
1,25 Everybody Service -
2-7-1-3 Tank filling - - - - -
2-7-1-3-1 Inlet valve type Tank filling on/off valve Tank-filling on/off
valve
Everybody Service -
Tank filling proportional valve
2-7-1-3-2 Minimum opening angle of
valve
0 … 100 % 0,1 Everybody Service -
2-7-1-3-3 Step width for valve actuation 0 … 100 % 0,1 Everybody Service -
2-7-1-4 Additional tank filling - - - - -