Fig. 7: Structure of electric cable
1 Wire end sleeve 2 Core
3 Cable
Table 14: Cable cross-sections of control terminals
Control terminal Core cross-section Maximum cable diameter
[mm]
Rigid and flexible cores
[mm
2
]
Flexible cores with wire end
sleeves
[mm
2
]
P4 terminal strip 0,2-1,5 0,75
9,5
24)
P7 terminal strip 0,2-2,5 0,25-1,5
Table 15: Power/connection cable properties
PumpDrive size Power
[kW]
Cable gland for Nominal
current
25)
, mains
[A]
Max. cable cross-
section for mains
power supply
26)27)
[mm²]
I
Nominal
28)
, motor
[A]
Mains
power
cable
Sensor
cable
Motor
cable
PTC
thermist
or
A
.. 000K55 .. 0,55 1,8 M25
M16
M25
M16
1,9 2,5
.. 000K75 .. 0,75 2,5 2,6
.. 001K10 .. 1,1 3,5 3,7
.. 001K50 .. 1,5 4,8 5,0
.. 002K20 .. 2,2 6,0 6,3
.. 003K00 .. 3 8,0 8,5
B .. 004K00 .. 4 10,0 M25 M16 M25 M16 10,5 2,5
.. 005K50 .. 5,5 13,0 13,7
.. 007K50 .. 7,5 16,5 17,3
C
.. 011K00 .. 11 25,0 M32 M16 M32 M16 26,5 10
.. 015K00 .. 15 31,0 32,6
.. 018K50 .. 18,5 39,0 41,0
.. 022K00 .. 22 45,0 47,3
D .. 030K00 .. 30 65,0 M40 M16 M40 M16 68,3 35
.. 037K00 .. 37 80,0 84,0
.. 045K00 .. 45 93,0 97,7
Length of motor connection cable
If PumpDrive is not mounted on the motor to be controlled, longer motor connection
cables may be required. The stray capacitance of the connection cables may result in
high-frequency discharge currents flowing to ground. The sum of the discharge
current and motor current may exceed the output-side rated current of PumpDrive.
24)
Impairment of protection provided by enclosure when cable diameters other than those specified are used.
25)
Observe the information on the use of line chokes provided in the Accessories and Optional Equipment section.
26)
Max. cable cross-section: 0.75 mm² for the signal cables for digital inputs/field bus interface/+24 V DC supply, digital/analog
outputs
27)
Max. cable cross-section: 1.5 mm² for the signal cables for volt-free relays/analog inputs
28)
PWM carrier frequency at a max. ambient temperature of 40 °C: – Sizes A and B: 4 k Hz – Sizes B and C: 2.5 kHz
5 Installation at Site