EasyManua.ls Logo

KSB PumpDrive - Page 67

KSB PumpDrive
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 61: Start and stop parameters in multiple pump configurations
Paramete
r
Description Possible settings Reference
to
Factory default
3-6-4-1
High load at low motor frequency 0..100 [%]
3-3-2-1
60 %
3-6-4-2
High load at high motor frequency 0..100 [%]
3-3-2-1
90 %
3-6-4-3
High load profile Linear
Square
Cubic
- Linear
3-6-4-4
High load time delay 0 - 30 [s] - 5 s
3-6-4-5
Function for high load warning No Function
Warning
Stop and Trip
- No Function
3-6-4-6
Low load at low motor frequency 0..100 [%]
3-3-2-1
30 %
3-6-4-7
Low load at high motor frequency 0..100 [%]
3-3-2-1
60 %
3-6-4-8
Low load profile Linear
Square
Cubic
- Linear
3-6-4-9
Low load time delay 0..30 [s] - 10 s
3-6-4-10
Function for low load warning No Function
Warning
Stop and Trip
- No Function
3-3-21
Nominal motor power 0,55..45 [kW] - Depending on the size
3-6-1-2
Lower limit for motor frequency 0 [%] to Frequency
High
(3-6-1-3)
3-11-4-1
50 %
3-6-1-3
Upper limit for motor frequency Frequency Low
(3-6-1-2)
to 100 [%]
3-11-4-1
100 %
3-11-4-1
Maximum output frequency 1 - 70 [Hz] - 50 Hz
7.1.3.2 Configuration example
The following parameterisation example applies to a multiple pump configuration
with a main pump, an auxiliary main pump and a slave pump. The PumpDrives used
are equipped as follows:
Table 62: Multiple pump configuration example
PumpDrive Role Control panel
1 Main pump with active master control panel Advanced
2 Auxiliary main pump with auxiliary master control panel Advanced
3 Slave pump Standard
The parameter settings of the individual PumpDrives have to be made/checked as
follows:
Parameterise PumpDrive1 with active master control panel
Table 63: Configuration example for multiple pump operation: PumpDrive 1
Parameter Description Value
3-1-7-4
Time value for identifying the control panel as the active master
control panel
1.0 s
3-2-1-1
Role in multiple pump configuration Auxiliary main pump
3-2-1-2
PumpDrive ID 1
3-7-1-2
Function of digital input 2 System start
3-10-1-3
Time value for identifying the control panel as the main pump 2.5 s
3-12-5-1
Maximum number of pumps running simultaneously 2
3-12-5-5
Pump changeover Enabled
Parameterise PumpDrive 3 using the active master control panel of PumpDrive 1:
Table 64: Configuration example for multiple pump operation: PumpDrive 3
Parameter Description Value
3-1-1-4
Selection of a PumpDrive from the multiple pump configuration Pump 3
3-2-1-1
Role in multiple pump configuration Standard slave
7 Commissioning/shutdown
PumpDrive
67 of 162

Table of Contents

Related product manuals