3 Product Description
3 Product Description
The flame monitor F130l is a safety device for the monitoring of flames (ignition or main flame)
using the ionisation method. In addition, it is also possible to connect it to optical sensors.
The flame monitor is used in combustion plants to record the burner flame in the combustion
chamber and signal the flame signal to the downstream burner control system by means of a
safety-oriented, potential-free relay output.
3.1 Proper Use - Conditions of Use
The flame monitor is preferably intended for use in stove systems. The evaluation device may
only be operated with the flame sensors approved in 4.2 Flame Sensors.
The monitoring of the following fuels is possible:
The flame scanner is not designed to switch off the fuel valves. The subsequent signal pro-
cessing must be carried out in the control system, which is adapted to suit the combustion
plant.
Please observe the following information when operating the flame monitor:
The safety information in this manual
Chapter 11.1 Technical Data in this manual.
Any other usage going beyond this is considered to be improper use. The plant operating com-
pany is liable for any damages that resulting from this.
1 F130I housing
2 LED display
3 Device connector
4 Top-hat rail mounting
Fuel Ionisation Optical
Oil - X
Gas X X
Biomass - X
Solid matter (wood, powdered coal...) - X
Chemical and other waste products - X
Combined fuels - X