5 Commissioning
5.2.5 Positioning of the ionisation electrode
Observe the following points when positioning the ionisation electrode (lance):
Select a position so that the sensor electrode as well as the counter electrode (burner noz-
zle possibly with additional electrodes for increasing the effective area) remain in contact
with the flame in the entire control range of the burner.
The sensor electrode should immerse into the hot part of the flame, however, the temper-
atures prevailing there should not exceed the lance specifications.
To check the optimal electrode position, the ionisation DC current is measured via the
shunt measuring principle at X14 or the 0/4..20mA output on terminal X14. For further in-
formation, see chapter 4.3 Functional DescriptionFlame intensity output.