29
7 Repairs
7 Repairs
WARNING!
Observe the safety instructions in chapter 2.
Disregard for these safety instructions can result in severe injuries or significant
physical damage.
When replacing the F130l or a flame sensor, it must be replaced by a device with the same
identification information.
Perform the following activities after replacing an evaluation device or a sensor:
• Check all electrical plug connections.
• Place burner into operation
• Check flame monitor for proper function
• Check reaction time for flame failure (switch-off test) analogue to commissioning.
Is there a correct switch-off within the safety time according to chapter 4.5 Control El-
ements ?
Create a log for the measurements and tests that have been performed.
This must also be confirmed by signature of the operator, if necessary.