2 General Safety Instructions
2.3 Product-specific Dangers
Electrical coupling with devices that are not mentioned in these instructions may only occur
after consulting with LAMTEC or with an expert.
WARNING!
The Gerät is not provided with a direct switch-off of the fuel valves.
The subsequent signal processing must be carried out in the control system, which is
adapted to suit the combustion plant.
The device may only be used with burner controllers that work according to DIN EN 298.
NOTICE
This product is state-of-the-art technology and complies with the generally accepted safety-
related rules and regulations. Every device is tested before delivery to ensure that it is working
properly and safely.
Only use this product when it is perfect condition and in accordance with the manual, the
prevailing regulations and guidelines and the applicable safety and accident prevention
regulations.
WARNING!
The F130I is a safety device. Only specialist staff of the manufacturer or people approved by
the manufacturer may intervene. No interventions by anyone else are permissible. This ap-
plies, in particular, in the event of a defective fuse.
WARNING!
Please observe the safety instructions to avoid personal injury and damage to property
and the environment!
Qualified specialist staff are required to carry out all activities (assembly, installation, ser-
vicing, etc.).
When installing the electrical accessories, do everything necessary to provide shock pro-
tection.
Make sure that the power cables are not interchanged between L and N.
The plug connectors X13, X14, X15 and X16 do not have a secure disconnection from the
mains voltage. To replace or disconnect the plug connectors, all poles of the plant must
be disconnected from the mains.
To ensure the electrical safety, the flame signal output and the alarm relay output on X11
must be supplied with the same potential.
Measuring circuits must feature a secure disconnect according to
EN 61140 "Protection against electric shock ..." for active parts; for this reason, use only
measurement and evaluation devices which have a double or reinforced insulation.
After each activity (e.g. assembly, installation, servicing, etc.), check the wiring and para-
metrisation to make sure it is in good working condition.
If the equipment is dropped or suffers impact, you should no longer commission it. The
safety functions may also be impaired but fail to show any obvious external damage.
The manufacturer of the burner or boiler ensures that the protection class/category IP40
or IP54 (for outdoor use) is achieved for the F130l during installation or where applicable