Page 28
CBX40UHV
ELECTRIC HEAT DATA - CBX40UHV-036
SINGLE PHASE ELECTRIC HEAT CBX40UHV-036
Model Number
No.
of
Stages
Volts
Input
kW
Input
1
Btuh
Input
2
Blower
Motor Full
Load Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
Circuit Circuit
1 2 1 2
4 kW
4 lbs.
ECB40-4 (55W89)
Terminal Block
ECB40-4CB (55W90)
35A Circuit breaker
1
208 3.0 10,250 5.6 25 - - -
4
25 - - -
220 3.4 11,450 5.6 26 - - -
4
30 - - -
230 3.7 12,550 5.6 27 - - -
4
30 - - -
240 4.0 13,650 5.6 28 - - -
4
30 - - -
5 kW
4 lbs.
ECB40-5 (34W87)
Terminal Block
ECB40-5CB (34W90)
35A Circuit breaker
1
208 3.8 12,800 5.6 30 - - -
4
30 - - -
220 4.2 14,300 5.6 31 - - - 35 - - -
230 4.6 15,700 5.6 32 - - - 35 - - -
240 5.0 17,100 5.6 34 - - - 35 - - -
6 kW
4 lbs.
ECB40-6 (34W88)
Terminal Block
ECB40-6CB (34W91)
40A Circuit breaker
1
208 4.5 15,400 5.6 35 - - -
4
35 - - -
220 5.0 17,100 5.6 35 - - -
4
35 - - -
230 5.5 18,800 5.6 37 - - - 40 - - -
240 6.0 20,500 5.6 39 - - - 40 - - -
8 kW
5 lbs.
ECB40-8 (34W89)
Terminal Block
ECB40-8CB (34W92)
50A Circuit breaker
1
208 6.0 20,500 5.6 44 - - -
4
45 - - -
220 6.7 22,900 5.6 45 - - -
4
45 - - -
230 7.3 25,100 5.6 47 - - - 50 - - -
240 8.0 27,300 5.6 49 - - - 50 - - -
9 kW
5 lbs.
ECB40-9CB (34W93)
60A Circuit breaker
2
208 6.8 23,100 5.6 48 - - -
4
50 - - -
220 7.6 25,800 5.6 50 - - -
4
50 - - -
230 8.3 28,200 5.6 52 - - - 60 - - -
240 9.0 30,700 5.6 54 - - - 60 - - -
12.5
kW
10 lbs.
ECB40-12.5CB (34W94)
(1) 30A & (1) 45A Circuit
breaker
2
208 9.4 32,000 5.6 26 38 30
4
40
220 10.5 35,800 5.6 27 40 30
4
40
230 11.5 39,200 5.6 28 42 30 45
240 12.5 42,600 5.6 29 44 30 45
15 kW
12 lbs.
ECB40-15CB (34W95)
(1) 35A & (1) 60A Circuit
breaker
2
208 11.3 38,400 5.6 30 45
4
30
4
45
220 12.6 43,000 5.6 31 48 35
4
50
230 13.8 47,000 5.6 32 50 35
4
50
240 15.0 51,200 5.6 33 52 35 60
20 kW
19 lbs.
ECB40-20CB (34W96)
(2) 60A Circuit breaker
2
208 15.0 51,200 5.6 48 50
4
50
4
50
220 16.8 57,300 5.6 50 53
4
50 60
230 18.4 62,700 5.6 52 55 60 60
240 20.0 68,200 5.6 54 57 60 60
THREE PHASE ELECTRIC HEAT
8 kW
5 lbs.
ECB40-8 (34W98)
Terminal Block
1
208 6.0 20,500 5.6 28 - - - 30 - - -
220 6.7 22,900 5.6 29 - - - 30 - - -
230 7.3 25,100 5.6 30 - - - 30 - - -
240 8.0 27,300 5.6 32 - - - 35 - - -
10 kW
6 lbs.
ECB40-10 (34W99)
Terminal Block
1
208 7.5 25,600 5.6 34 - - - 35 - - -
220 8.4 28,700 5.6 35 - - - 35 - - -
230 9.2 31,400 5.6 36 - - - 40 - - -
240 10.0 34,100 5.6 38 - - - 40 - - -
15 kW
12 lbs.
ECB40-15CB (35W00)
50A Circuit breaker
1
208 11.3 38,400 5.6 47 - - - 50 - - -
220 12.6 43,000 5.6 48 - - - 50 - - -
230 13.5 47,000 5.6 50 - - - 50 - - -
240 15.0 51,200 5.6 53 - - -
4
60 - - -