E84AYCER communication manual (PROFINET)
Installation
Electrical installation
32 L EDS84AYCER EN 2.0 - 11/2010
5.2.5 External voltage supply
The communication module can be externally supplied with voltage via separate supply
cables at the 2-pole plug connector (X255).
External voltage supply of the communication module is necessary if the bus
communication is to continue when the supply of the standard device fails.
It is not possible to access parameters of a standard device disconnected from the
mains.
Wiring the X255 plug connector
[5-11] Wiring of the 2-pole plug connector with spring connection
How to wire the plug connector with spring connection:
1. Press a screwdriver into the groove below the contact slot and keep it pressed.
2. Insert the supply cable into the contact slot.
3. Remove the screwdriver from the groove.
Note!
With external voltage supply, always use a separate power supply unit, safely
separated in accordance with EN 61800-5-1 in every control cabinet ("SELV" /
"PELV").
Stop!
Only wire the plug connector if the standard device is disconnected from the
mains.