E84AYCER communication manual (PROFINET)
Commissioning
Configuring the PROFINET IO controller
6.2 Configuring the PROFINET IO controller
The host system must be configured before communication with the communication
module is possible.
Configuration for device control
For the configuration of PROFINET, the current PROFINET device description file (XML) of
the E84AYCER communication module (PROFINET) has to be imported in the IO controller.
The device description file GSDML-Vx.z-Lenze-8400PNabb-yyyymmdd.xml can be found
on the Lenze Internet pages further on in the "Services & Downloads" area under:
www.Lenze.com
Definition of the user data length
The user data length is defined during the initialisation phase of the IO controller.
The Inverter Drives 8400 support the configuration of max. 16 process data words (max.
32 bytes).
Description of the device data base file
Example of device data base file selection
"PCD (8W) AR cons." = process data words (8 words)
Tip!
A detailed description of the consistency is provided in the chapter "Consistent
parameter data" ( 64).
Wildcards in the file name: "GSDML-Vx.z-Lenze-8400PN100-yyyymmdd.xml"
x Main version of the GSDML scheme used
z Subversion of the GSDML scheme used
a Major version of the software version
bb Minor version of the software version
yyyy Year
mm Month
dd Day
Selection text Parameter data
(with consistency)
Process data
(with consistency)
Assigned
I/O memory
PCD (nW) AR cons. - n words n words
n = 1 ... 16 process data words

Table of Contents