E84AYCER communication manual (PROFINET)
Commissioning
Setting the IP configuration
38 L EDS84AYCER EN 2.0 - 11/2010
6.4 Setting the IP configuration
If the communication module is to be made accessible via its IP parameters, the IP address,
subnet mask, and gateway address must either be assigned by the IO controller via
PROFINET or set manually in the »Engineer«.
In the »Engineer« the IP parameters are set under the Settings tab.
Note!
The IP parameters are written to codes C13000 (IP address), C13001 (subnet
mask), and C13002
(gateway address) as decimal values.
Use the [int] buttons to the right of the input fields to change to the decimal
code representation.
The assignment of invalid combinations of IP address, subnet mask, and
gateway address can have the consequence that no connection to the
PROFINET can be established.
In the case of impermissible settings the red LED "BE" (Fieldbus status displays
( 68)
) blinks.
If the IP parameters are assigned by the IO controller via PROFINET the change
is activated immediately. The current parameter values are displayed in the
corresponding codes.