Installation
4-22
BA9300POS EN 2.3
4.2.8.3 Connection diagrams
Connection of analog signals
Analog signals are connected via the 2 x 4-pole terminal block X6.
Depending on the use of the analog inputs, the jumper of X3 must be set accordingly.
Connection for external supply voltage
+
1234 7 63
100k
100k
100k
X6
 
GND1 GND1
+
X6
3,3nF
100k
7
U
62
U
242R
X3
93XX
==
GND1
STOP!
• The maximum permitted voltage difference between an external voltage
source and the GND1 (terminal X6/7) of the controller is 10V (common mode).
• The maximum permitted voltage difference between GND1 (terminal X6/7)
and the PE of the controller is 50V.
+
1234
100k
 
GND1
+
X6
3,3nF
100k
7
242R
==
93XX
Limit the voltage difference
• by overvoltage clamping components or
• by direct connection of terminal(s) X6/2, X6/4 and X6/7 to GND1 and PE (see
figure).
Connection for internal voltage supply
1234 7 63
100k
100k
100k
X6
 
GND1
GND1
X6
3,3nF
100k
7
U
62
U
242R
X3
10k
10k
93XX
GND1
Configuration of the internal voltage supply:
• Set a freely assignable analog output (AOUTx) to HIGH level.
• E. g. terminal X6/63: Assign FIXED100% to C0436
^
4-20
10V are thus applied to terminal X6/63.
Tip!
Use one of the predefined configurations in C0005 for this application. The
output X3/63 is assigned automatically with FIXED100% (corresponds to 10 V at
output X6/63) by C005 = XX1X (e. g. 1010 for speed control with control via
terminals).