Commissioning
5-10
BA9300POS EN 2.3
5.6.5 Controller enable
• The controller is enabled only when all sources of the controller inhibit are reset.
– When the controller is enabled, the green LED on the controller is illuminated.
• For the display of active sources of a controller inhibit see Chapter “Troubleshooting”. (
^
8-1)
The following table shows the conditions for controller enable:
Source controller
inhibit
Controller inhibited Controller enabled Note
Te rmina l X5/ 28 0 V ... +4 V +13 V... +30 V -
Fault In case of TRIP
In case of Message
TRIP reset Check, see
^
8-1
System bus (CAN) Transmission of the control information INHIBIT via
C0135
Transmission of the control information ENABLE via
C0135
^
Manual
Field bus module See operating instructions of the corresponding fieldbus module -
Tip!
All sources of controller the inhibit act like a series connection of switches, independent of each
other.
Stop!
When the internal control structure is changed, another terminal assignment may result.