Commissioning
5-30
BA9300POS EN 2.3
5.11.2.1 Password protection
Code LCD
Possible settings
IMPORTANT
Lenze Selection
C0094 Password 0 0 {1} 9999 Password
• Parameter access protection for the operating
module. When the password is activated, only
the codes of the user menus can be accessed.
For further selection possibilities see C0096
[C0096]
1
2
AIF protect.
CAN protect.
0
0
0 Nopasswordprotection
1 Read protection
2 Write protection
3 Read/Write protection
Extended password protection for bus systems
with activated password (C0094).
• All codes in the user menu can be accessed.
You can restrict the code access via the operating module using the password protection in C0094.
• Reading C0094 using the operating module:
– C0094 = 0: password protection is not activated.
– C0094 = 9999: password protection is activated.
• Activate password protection:
– Enter four-digit number in C0094.
–ConfirmusingSH+PRG.
• Deactivate password protection:
– Enter four-digit number again.
– All other inputs are refused.
Effect
• Working with the operating module:
– The codes listed in the USER menu can still be read and changed.
– All other codes are no longer displayed.
• Working with the fieldbus:
– It is possible to extend the protection for codes via the fieldbus under C0096/1 (AIF) and
C0096/2 (CAN).