14.2.5 SPEED REFERENCE SELECTION
AUTO/MAN vs. LOCAL/REMOTE
For the MC3000 Series drive, operating in standard (non-PID) mode, AUTO/MAN refers to
speed control, and LOCAL/REMOTE refers to START/STOP control. AUTOMATIC and
MANUAL speed control selection is affected by whether the drive is in LOCAL or REMOTE
mode, as described below. Refer to Section 19 - MC3000 PID SETPOINT CONTROL for
a complete description of drive operation when using the PID control function.
AUTO/MAN SELECTION IN LOCAL MODE
In LOCAL mode (keypad start/stop control), AUTOMATIC and MANUAL selection is
determined by Parameter 28 - AUTO/MAN. When Parameter 28 is set to A/M LOC or
A/M SPD, the AUTO/MAN key on the keypad is active and can be used to toggle between
MANUAL (keypad) and AUTOMATIC (0-10 VDC, 4-20 mA, or preset speeds) speed
control. This is done by pressing the AUTO/MAN key to select the desired mode, and
then pressing the ENTER key within three seconds to confirm the change.
When AUTOMATIC mode is selected, one of the TB-13 input selects must be programmed
to select the desired speed reference, and that TB-13 terminal must be closed to TB-2.
The drive will then respond to the automatic speed reference. If the contact closure is
not made between the TB-13 terminal and TB-2, the drive will remain in AUTO mode, but
speed control will default to the keypad. Therefore, if the Form C relay or open-collector
outputs are set to indicate AUTO/MAN mode, they will still indicate AUTO mode.
AUTO/MAN SELECTION IN REMOTE MODE
In REMOTE mode (terminal strip start/stop control), speed control is either selected using
the AUTO/MAN key (Parameter 28 - AUTO/MAN must be set to A/M SPD to do this), or
by using the TB-13 input selects.
If AUTOMATIC mode is selected using the AUTO/MAN key (Parameter 28 - AUTO/MAN
must be set to A/M SPD to do this), and a speed reference is not selected using one of
the TB-13 input selects, the drive will remain in AUTO mode, but speed control will default
to the keypad. Therefore, if the Form C relay or open-collector outputs are set to indicate
AUTO/MAN mode, they will still indicate AUTO mode.
If the drive is configured to select AUTOMATIC mode by using one of the the TB-13 input
selects, closing the TB-13 terminal to TB-2 selects AUTOMATIC mode, and opening the
TB-13 terminal selects MANUAL (keypad) mode. Therefore, if the TB-13 terminal is not
closed to TB-2, and the Form C relay or open-collector outputs are set to indicate AUTO/
MAN mode, they will indicate MANUAL mode.
0 - 10 VDC and 4 - 20 mA INPUT SIGNALS
TB-13A, TB-13B, and TB-13C can all be programmed to select 0-10 VDC or 4-20 mA input.
PRESET SPEEDS
TB-13A can be programmed to select SPEED #1, TB-13B to select SPEED #2, and
TB-13C to select SPEED #3. Closing any two of these terminals to TB-2 will select
SPEED #4. Refer to Parameters 1-4: SPEED #1 - #4 in Section 18 - DESCRIPTION
OF PARAMETERS.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze AC Tech M3103S and is the answer not in the manual?

Lenze AC Tech M3103S Specifications

General IconGeneral
BrandLenze
ModelAC Tech M3103S
CategoryController
LanguageEnglish

Related product manuals