Appendix
Code table
14−14
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0007
uSEr
(cont.)
E4 E3 E2 E1
41
JOG1/3 DCB TRIP set DFIN1−ON
42
QSP DCB TRIP set DFIN1−ON
43
CW/CCW QSP TRIP set DFIN1−ON
44
UP DOWN PAR DFIN1−ON
45
CW/CCW QSP PAR DFIN1−ON
46
H/Re PAR QSP JOG1/3
47
CW/QSP CCW/QSP H/Re JOG1/3
48
PCTRL1− OFF
DCB
PCTRL1−I−OFF
DFIN1−ON
49
PCTRL1− OFF
JOG1/3 QSP DFIN1−ON
50
PCTRL1− OFF
JOG1/3
PCTRL1−I−OFF
DFIN1−ON
51
DCB PAR
PCTRL1−I−OFF
DFIN1−ON
255 Free configuration under C0410 Only display
Do not change C0007 since settings under
C0410 can be lost
C0008
Fixed configuration
− relay output K1
(relay, motec
version 151) or
Digital switching
output K1 (motec
versions 152, 153)
1
Change of C0008 is copied into C0415/1.
Free configuration in C0415/1 sets
C0008 = 255!
7−73
0 Ready for operation (DCTRL1−RDY)
1 TRIP error message (DCTRL1−TRIP)
2 Motor is running (DCTRL1−RUN)
3 Motor is running / CW rotation (DCTRL1−RUN−CW)
4 Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
5 Output frequency = 0 (DCTRL1−NOUT=0)
6 Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
7 Values have fallen below frequency threshold
Q
min
(f < C0017) (PCTRL1−QMIN)
LOW active
8 I
max
limit reached (MCTRL1−IMAX)
C0014 = 5: torque setpoint reached
9 Overtemperature (ϑ
max
−5 °C)
(DCTRL1−OH−WARN)
10 Values have fallen below TRIP or Q
min
or pulse
inhibit (IMP) (DCTRL1−TRIP−QMIN−IMP)
11 PTC warning (DCTRL1−PTC−WARN)
12 Apparent motor current < current threshold
(DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
13 Apparent motor current < current threshold and
output frequency > Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
14 Apparent motor current < current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT<ILIM)−RFG1=0)
15 Motor phase failure warning (DCTRL1−LP1−WARN)
16 Minimum output frequency reached (f C0010)
(PCTRL1−NMIN)
LOW active
255 Free configuration in C0415/1 Read only
Do not change C0008 since settings in
C0415/1 may get lost

Table of Contents