Appendix
Code table
14−15
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0009*
Controller address 1 1 {1} 99 Only for communication modules on the AIF
interface:
LECOM−A (RS232) E82ZBL
LECOM−A/B/LI 2102
PROFIBUS−DP 213x,
System bus (CAN) 217x
During operation with the E82ZAFCC
system bus function module the node
address must be set under C0350.
C0010
uSEr
Minimum output
frequency
0.00 0.00
à 14.5 Hz
{0.02 Hz} 650.00
C0010 is not effective with bipolar
setpoint selection (−10 V ... + 10 V)
C0010 only defines the analog input 1
As of software 3.5: If C0010 > C0011,
the drive does not start running with
controller enable.
à Speed setting range 1 : 6 for Lenze
geared motors: Setting absolutely
required for operation with Lenze geared
motors.
7−21
C0011
uSEr
Maximum output
frequency
50.00 7.50
à 87 Hz
{0.02 Hz} 650.00
C0012
uSEr
Acceleration time
main setpoint
5.00 0.00 {0.02 s} 1300.00 Reference: frequency change 0 Hz ...
C0011
Additional setpoint ð C0220
Acceleration times can be activated via
digital signals ð C0101
7−24
C0013
uSEr
Deceleration time
main setpoint
5.00 0.00 {0.02 s} 1300.00 Reference: frequency change
C0011 ... 0 Hz
Additional setpoint ð C0221
Deceleration times can be activated via
digital signals ð C0103
7−24
C0014
Operating mode 2
2 V/f characteristic control V ~ f
(linear characteristic with constant V
min
boost)
Commissioning is possible without
identifying motor parameters
Advantage of identification with C0148:
Improved smooth running at low
speeds
V/f rated frequency (C0015) and slip
(C0021) are calculated and saved.
They must not be entered
7−2
3 V/f characteristic control V ~ f
2
(square−law characteristic with constant V
min
boost)
4 Vector control
In case of the first selection enter the
motor data and identify them with
C0148
Otherwise, commissioning is not
possible
When C0014 = 5, C0019 must be set = 0
(automatic DC injection brake is
deactivated)
5 Sensorless torque control with speed limitation
Torque setpoint via C0412/6
Speed limitation via setpoint 1 (NSET1−N1) if
C0412/1 is assigned, otherwise via maximum
frequency (C0011)
C0015
uSEr
V/f rated frequency 50.00 7.50 {0.02 Hz} 960.00 C0015 is calculated and stored under
C0148 when the motor parameters are
identified
Setting applies to all mains voltages
permitted
7−4
7−8
C0016
uSEr
V
min
boost à 0.00 {0.01 %} 40.00 à Depending on the controller
Setting applies to all mains voltages
permitted
7−4
C0017 Frequency
threshold Q
min
0.00 0.00 {0.02 Hz} 650.00 Programmable frequency threshold
Reference: Setpoint
Signal output configuration under C0415
C0018
Switching
frequency
2
0 2 kHz sin
General rule:
The lower the switching frequency the
lower the power loss
higher the noise generation
Only operate mid−frequency motors at 8
kHz sin or 16 kHz sin (C0018 = 2 or 3)!
7−14
1 4 kHz sin
2 8 kHz sin
low noise generation
3 16 kHz sin