Appendix
Code table
14−16
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0019 Operating threshold
− automatic DC
injection brake
(auto DCB)
0.10 0.00
= inactive
{0.02 Hz} 650.00 Hold time ð C0106
Deactivate automatic DC injection brake
(auto DBC):
at active lower frequency limitation
(C0239)
at operating mode C0014 = 5
7−30
C0021 Slip compensation 0.0 −50.0 {0.1 %} 50.0 C0021 is calculated and stored under
C0148 when the motor parameters are
identified
7−13
C0022 I
max
limit (motor
mode)
150 30 {1 %} 150 Only 8200 vector 15 ... 90 kW:
If C0022 = 150 %, 180 % I
r
are available
for max. 3 s. after controller enable
7−23
C0023 I
max
−limit in the
generator mode
150 30 {1 %} 150 C0023 = 30 %: function is inactive, if
C0014 = 2, 3:
7−23
C0026* Offset analog input
1 (AIN1–OFFSET)
0.0 −200.0 {0.1 %} 200.0 Settings for X3/8 and X3/1U, X3/1I
The max. limit of the setpoint value
range of C0034 equals 100 %
C0026 and C0413/1 are identical
7−34
C0027* Gain analog input 1
(AIN1−GAIN)
100.0 −1500.0 {0.1 %} 1500.0 Settings for X3/8 and X3/1U, X3/1I
100.0 % = Gain 1
Inverse setpoint selection by negative
gain and negative offset
C0027 and C0414/1 are identical
7−34
C0034*
uSEr
Setpoint selection
range
Standard–I/O (X3/8)
−24−
Observe the switch position of the function
module!
7−34
0
0 Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1 Current 4 ... 20 mA Changing the direction of rotation is only
possible with a digital signal.
2 Bipolar voltage −10 V ... +10 V Minimum output frequency (C0010) not
effective
Individual adjustment of offset and gain
3 Current 4 ... 20 mA open−circuit monitored TRIP Sd5, if I < 4 mA
Changing the direction of rotation is only
possible with a digital signal.
C0034*
(A)
uSEr
Setpoint selection
range
Application I/O
Observe the jumper setting of the function
module!
7−34
1 X3/1U, X3/1I
0
0 Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I 1 Bipolar voltage −10 V ... +10 V Minimum output frequency (C0010) not
effective
2 Current 0 ... 20 mA
3 Current 4 ... 20 mA Changing the direction of rotation is only
possible with a digital signal.
4 Current 4 ... 20 mA open−circuit monitored Changing the direction of rotation is only
possible with a digital signal.
TRIP Sd5 if I < 4 mA
C0035*
DC injection brake
(DCB) control mode
0
0 Brake voltage selection under C0036
Hold time ð C0107 7−30
1 Brake current selection under C0036
C0036 Voltage/current DC
injection brake
(DCB)
à 0.00 {0.01 %} 150.00 % à Depending on the controller
Reference M
r
, I
r
Setting applies to all mains voltages
permitted
7−30
C0037 JOG1 20.00 −650.00 {0.02 Hz} 650.00
JOG = fixed setpoint
Additional fixed setpoints ð C0440
7−43
C0038 JOG2 30.00 −650.00 {0.02 Hz} 650.00
C0039 JOG3 40.00 −650.00 {0.02 Hz} 650.00
C0040*
Controller inhibit
(CINH)
−0− Controller inhibited (CINH)
Controller can only be enabled if X3/28 =
HIGH
7−20
−1− Controller enabled (CINH)