Appendix
Code table
14−17
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0043*
TRIP reset
0 No current error
Reset active error with C0043 = 0
1 Active fault
C0044* Setpoint 2
(NSET1−N2)
−650.00 {0.02 Hz} 650.00 The value set will be lost when
switching the mains!
Selection, if C0412/2 = FIXED−FREE (not
assigned)
Display if C0412/2 is linked with a signal
source
7−45
C0046* Setpoint 1
(NSET1−N1)
−650.00 {0.02 Hz} 650.00 The value set will be lost when
switching the mains!
Selection, if C0412/1 = FIXED−FREE (not
assigned)
Display if C0412/1 is linked with a signal
source
7−45
C0047* Torque setpoint or
torque limit value
(MCTRL1−MSET)
400 0 {1 %} 400 The value set will be lost when
switching the mains!
7−10
Ref.: Rated motor torque detected by motor parameter
identification
Control mode "Sensorless torque control"
(C0014 = 5):
Torque setpoint selection if C0412/6 =
FIXED−FREE (not assigned)
Torque setpoint display if C0412/6 is
linked with a signal source
Control mode "V/f characteristic control" or
"Vector control" (C0014 = 2, 3, 4):
Torque limit value is displayed if
C0412/6 is linked with a signal source
C0047 = 400 is displayed if C0412/6 =
FIXED−FREE (not assigned)
C0049* Additional setpoint
(PCTRL1−NADD)
−650.00 {0.02 Hz} 650.00 The value set will be lost when
switching the mains!
Selection, if C0412/3 = FIXED−FREE (not
assigned)
Display if C0412/3 is linked with a signal
source
C0050*
uSEr
Output frequency
(MCTRL1−NOUT)
−650.00 {Hz} 650.00 Only display: Output frequency without slip
compensation
C0051* Output frequency
with slip
compensation
(MCTRL1−NOUT
+SLIP) or
act. process
controller value
(PCTRL1−ACT)
−650.00 {0.02 Hz} 650.00 The value set will be lost when
switching the mains!
Operation without process controller
(C0238 = 2):
Display only: Output frequency with slip
compensation (MCTRL1−NOUT+SLIP)
Operation with process controller
(C0238 = 0, 1):
Selection, if C0412/5 = FIXED−FREE (not
assigned)
Display if C0412/5 is linked with a signal
source
7−54
C0052* Motor voltage
(MCTRL1−VOLT)
0 {V} 1000 Only display
C0053* DC−bus voltage
(MCTRL1−DCVOLT)
0 {V} 1000 Only display
C0054* Apparent motor
current
(MCTRL1−IMOT)
0.0 {A} 2000.0 Only display
C0056* Controller load
(MCTRL1−MOUT)
−255 {%} 255 Only display
Under C0311 you can change the display
value for the operating modes vector
control or sensorless torque control.