Appendix
Code table
14−18
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0061* Heatsink
temperature
0 {°C} 255 Only display
If the heatsink temperature is >
max
−
5 °C:
– The warning
OH will be sent.
– The chopper frequency will be
reduced to 4 kHz, if C0144 = 1
If the heatsink temperature is >
max
:
– Controller sets TRIP
OH
C0070 Process controller
gain
1.00 0.00
= P component not
active
{0.01} 300.00 7−50
C0071 Process controller
readjustment time
100 10 {1} 9999
= I component not
active
7−50
C0072 Differential
component of
process controller
0.0 0.0
= D component not
active
{0.1} 5.0 7−50
C0074 Process controller
influence
0.0 0.0 {0.1 %} 100.0 7−50
C0077* Gain I
max
controller 0.25 0.00
= P component not
active
{0.01} 16.00 7−56
C0078* Integral action time
I
max
controller
65
à 130
12 {1 ms} 9990
= I component not
active
à Only 8200 vector 15 ... 90 kW 7−56
C0079 Oscillation damping 2 0 {1} 140 7−16
C0084 Motor stator
resistance
0.000 0.000 {0.001 } 64.000
7−48
0.0 0.0 {0.1 m } 6500.0 Only 8200 vector 15 ... 90 kW
C0087 Rated motor speed à 300 {1 rpm} 16000 à Depending on the controller 7−48
C0088 Rated motor
current
à 0.0 {0.1 A} 650.0 à Depending on the controller
0.0 ... 2.0 x rated output current of the
controller
7−48
C0089 Rated motor
frequency
50 10 {1 Hz} 960 7−48
C0090 Rated motor
voltage
à 50 {1 V} 500 à 230 V with 230 V controllers,
400 V with 400 V controllers
7−48
C0091 Motor cos ϕ
à 0.40 {0.1} 1.0 à Depending on the controller 7−48
C0092 Motor stator
inductance
0.0 0.000 {0.1 mH} 200.0
7−48
0.00 0.00 {0.01 mH} 200.00 Only 8200 vector 15 ... 90 kW
C0093* Controller type xxxy Only display
xxx = Power taken from nameplate (e.
g. 551 = 550 W)
y = Voltage class (2 = 240 V, 4 = 400 V)
C0094* User password 0
= no password
protection
{1} 9999 1 ... 9999 = Free access to user menu only 6−7
C0099* Software version x.y Only display
x = Main version, y = Index