Appendix
Code table
14−21
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0114
Level inversion −
digital inputs
0
0 Level inversion switched off By entering the sum of the selected
values you can invert several inputs.
C0114 and C0411 are the same
The "Change over parameter set"
cannot be inverted!
1 E1 inverted
2 E2 inverted
4 E3 inverted
8 E4 inverted
16 E5 inverted Only application I/O
32 E6 inverted Only application I/O
64 T1/T2 inverted Only connect potential−free switches to
T1/T2.
T1/T2 is active when the switch is open.
C0117
Fixed configuration
of digital output A1
(DIGOUT1)
0
Changes of C0117 will be copied to
C0415/2. Free configuration under
C0415/2 sets C0117 =255!
7−73
0 ... 16 see C0008
255 Free configuration under C0415/2 Only display
Do not change C0117 since settings under
C0415/2 can be lost
C0119
−25−
Configuration of
motor temperature
monitoring (PTC
input) / earth fault
detection
0
0 PTC input not active
Earth fault detection
active
Signal output configuration under C0415
If several parameter sets are used, the
monitoring must be separately adjusted
for each parameter set.
Deactivate the earth fault detection, if it
has been activated unintentionally.
If the earth fault detection is active, the
motor starts after controller enable with
a delay of approx.40 ms.
7−84
1 PTC input active,
TRIP set
2 PTC input active,
Warning set
3 PTC input not active
Earth fault detection
inactive
4 PTC input active,
TRIP set
5 PTC input active,
Warning set
C0120 I
2
t switch−off 0 0
= not active
{1 %} 200 Reference: Apparent motor current (C0054)
Ref. to active motor current (C0056)
possible, see C0310
7−82
C0125*
Baud rate 0
LECOM System bus (CAN) 217x
Only for communication modules on the AIF
interface:
LECOM−A (RS232) E82ZBL
LECOM−A/B/LI 2102
System bus (CAN) 217x
During operation with the E82ZAFCC
system bus function module the baud
rate must be set under C0351.
0 9600 baud 500 kbaud
1 4800 baud 250 kbaud
2 2400 baud 125 kbaud
3 1200 baud 50 kbaud
4 19200 baud 1000 kbaud
C0126*
Response in the
event of a
communication
error
10
Monitored communication channel By entering the sum of the selected values
you can activate a monitoring combination
0 All monitoring is deactivated
1 Process channel of the AIF interface Communication abort at active monitoring
activates TRIP CE0
2 Internal communication between function module
on FIF and controller
Communication abort at active monitoring
activates TRIP CE5
4 Communication (bus OFF) at operation with
system bus function module (CAN) on FIF
Communication abort at active monitoring
activates TRIP CE6
8 Remote parameter setting via C0370 at operation
with function module system bus (CAN) on FIF
Communication abort at active monitoring
activates TRIP CE7
C0127
Setpoint selection 0
0 Absolute setpoint selection in Hz via C0046 or
process data channel
1 Setpoint selection normalised via C0141 (0... 100
%) or process data channel (±16384 = C0011)
C0128 Service code Modifications only by Lenze Service!