Appendix
Code table
14−25
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0156* Current threshold 0 0 {1 %} 150 Programmable current threshold
Reference: Rated controller current
Signal output configuration under C0008
or C0415
The reference values for vector control
and sensorless speed control can be
changed under C0311 (as of software
version 3.1).
C0161* Active error
Display history buffer contents
Keypad: three−digit, alpha numerical
fault detection
9371BB keypad: LECOM fault number
8−1
C0162* Last fault
C0163* Last but one fault
C0164* Last but two fault
C0168* Actual fault History buffer displays "active error"
Keypad: three−digit, alpha numerical
fault detection
9371BB keypad: LECOM fault number
8−1
C0170
Configuration TRIP
reset
0
0 TRIP reset by mains switching, , LOW–signal
at X3/28, via function module or communication
module
TRIP reset via function module or
communication module with C0043,
C0410/12 or C0135 bit 11.
Auto TRIP reset after the time set under
C0171.
8−7
1 like 0 and additional auto TRIP reset
2 TRIP reset through mains switching, via function
module or communication module
3 TRIP reset by mains switching
C0171 Delay for auto−TRIP
reset
0.00 0.00 {0.01 sec} 60.00
C0174*
Switching threshold
− brake chopper
100
78 {1 %} 110
Only active with 8200 motec 3 ... 7.5 kW
and 8200 vector 0.55 ... 11 kW, version
for 400/500 V mains voltage
100 % = switching threshold DC 790 V
110 % = brake chopper switched off
U
DC
= switching threshold in V DC
The recommended setting considers
max. 10 % mains overvoltage
11−1
Required setting
U
mains
[3/PE AC xxx V]
380
400
415
440
460
480
500
C0174
[%]
78
81
84
89
93
97
100
U
DC
[V DC]
618
642
665
704
735
767
790
C0178*
Operating time {h} Only display
Total duration terminal 28 (CINH) = HIGH
C0179* Power−on time {h} Only display
Total time mains on
C0181* Process controller
setpoint 2
(PCTRL1−SET2)
0.00 −650.00 {0.02 Hz} 650.00 7−53
C0182* Integration time
S–ramps
0.00 0.00 {0.01 s} 50.00 C0182 = 0.00: Linear ramp function
generator operation
C0182 > 0.00: S−shaped ramp function
generator (smooth)
7−24
C0183* Diagnostics
0 No fault
Only display
102 TRIP active
104 Message "Overvoltage (OU)" or "Undervoltage
(
LU)" active
142 Pulse inhibit
151 Quick stop active
161 DC−injection brake active
250 Warning active
C0184* Frequency
threshold
PCTRL1−I−OFF
0.0 0.0 {0.1 Hz} 25.0 If the output frequency < C0184, the
I component of the process controller
will be switched off
0.0 Hz = Function not active
7−53