Appendix
Code table
14−43
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0419
(cont.)
Possible analog signals for C0419 7−59
0 Output frequency (MCTRL1−NOUT+SLIP) 6 V/12 mA/5.85 kHz C0011
1
Device utilisation (MCTRL1−MOUT) at V/f
characteristic control (C0014 = 2 or 3)
3 V/6 mA/2.925 kHz Rated active inverter
current (active current/C0091)
Actual motor torque (MCTRL1−MACT) with vector
control (C0014 = 4) or sensorless torque control
(C0014 = 5)
3 V/6 mA/2.925 kHz rated motor torque
2 Apparent motor current (MCTRL1−IMOT) 3 V/6 mA/2.925 kHz rated inverter
current
3 DC−bus voltage (MCTRL1−DCVOLT) 6 V/12 mA/5.85 kHz DC 1000 V (400 V
mains)
6 V/12 mA/5.85 kHz DC 380 V (230 V
mains)
4 Motor power (MCTRL1−PMOT) 3 V/6 mA/2.925 kHz rated motor power
5 Motor voltage (MCTRL1−VOLT) 4.8 V/9.6 mA/4.68 kHz rated motor
voltage
6 1/output frequency (1/C0050) (MCTRL1−1/NOUT) 2 V/4 mA/1.95 kHz 0.5 C0011
7 Output frequency within adjusted limits
(DCTRL1−C0010...C0011)
0 V/0 mA/4 mA/0 kHz f = f
min
(C0010)
6 V/12 mA/5.85 kHz f = f
max
(C0011)
8
Operation with process controller (C0238 = 0, 1):
Actual process controller value (PCTRL1−ACT)
6 V/12 mA/5.85 kHz C0011
Operation without process controller (C0238 =
2):
Output frequency without slip (MCTRL1−NOUT)
C0419
(cont.)
Possible analog signals for C0419
Selection 9 ... 25 correspond to the digital
functions of the relay output K1 or the
digital switching output K1
(C0008) or the
digital output A1 (C0117):
LOW = 0 V/0 mA/4 mA/ 0 kHz
HIGH = 10 V/20 mA/10 kHz
7−59
9 Ready for operation (DCTRL1−RDY)
10 TRIP error message (DCTRL1−TRIP)
11 Motor is running (DCTRL1−RUN)
12 Motor is running / CW rotation (DCTRL1−RUN−CW)
13 Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
14 Output frequency = 0 (DCTRL1−NOUT=0)
15 Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
16 Values have fallen below frequency threshold
Q
min
(f < C0017) (PCTRL1−QMIN)
LOW active
17 I
max
limit reached (MCTRL1−IMAX)
C0014 = −5−: Torque setpoint reached
18 Overtemperature (
max
− 5 °C)
(DCTRL1-OH-WARN)
19 TRIP or Q
min
or pulse inhibit (IMP) active
(DCTRL1−TRIP−QMIN−IMP)
20 PTC warning (DCTRL1−PTC−WARN)
21 Apparent motor current < current threshold
(DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
22 Apparent motor current < current threshold and
output frequency > Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
23 Apparent motor current < current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)
24 Motor phase failure warning (DCTRL1−LP1−WARN)
25 Minimum output frequency reached (f C0010)
(PCTRL1−NMIN)
LOW active