Appendix
Code table
14−44
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0419
(cont.)
Possible analog signals for C0419 7−59
26 Output frequency normalised without slip
(MCTRL1−NOUT−NORM)
27 Output frequency without slip (MCTRL1−NOUT)
6 V/12 mA/5.85 kHz C0011
28 Actual process controller value (PCTRL1−ACT)
29 Process controller setpoint (PCTRL1−SET1)
6 V/12 mA/5.85 kHz C0011
30 Process controller output without feedforward
control (PCTRL1−OUT)
31 Ramp function generator input (NSET1−RFG1−IN)
32 Ramp function generator output (NSET1−NOUT)
33 (A) PID controller output (PCTRL1−PID−OUT)
34 (A) Process controller output (PCTRL1−NOUT)
35 Input signal at X3/8 (standard I/O) or X3/1U or
X3/1I (application I/O), assessed with gain
(C0414/1 or C0027) and offset (C0413/1 or
C0026) (AIN1−OUT)
6 V/12 mA/5.85 kHz maximum value of
analog input signal (5 V, 10 V, 20 mA,
10 kHz)
Condition: The gain of the analog input or
frequency input is set to:
C0414/x, C0426 = 100 %
36 Input signal at frequency input X3/E1 and X3/E2,
assessed with gain (C0426) and offset (C0427)
(DFIN1−OUT)
37 Motor potentiometer output(MPOT1−OUT)
38 (A) Input signal at X3/2U or X3/2I, assessed with gain
(C0414/2) and offset (C0413/2) (AIN2−OUT)
40 AIF input word 1 (AIF−IN.W1)
Setpoints to the controller from
communication module on AIF
10 V/20 mA/10 kHz 1000
41 AIF input word 2 (AIF−IN.W2)
50 CAN−IN1.W1 or FIF−IN.W1
Setpoints to controller from function module
on FIF
10 V/20 mA/10 kHz 1000
51 CAN−IN1.W2 or FIF−IN.W2
52 CAN−IN1.W3 or FIF−IN.W3
53 CAN−IN1.W4 or FIF−IN.W4
60 CAN−IN2.W1
61 CAN−IN2.W2
62 CAN−IN2.W3
63 CAN−IN2.W4
255 Not assigned (FIXED−FREE)